INFINITE UPSIDE

Infrastructure and business

From Landfill Gas to a Usable Industrial Fuel

The opportunity depends on a maintained route from the waste mass to equipment that can use what arrives.

A factory can use landfill gas only after the gas has completed a fairly demanding journey. It has to form in the waste, reach collection equipment, travel through a network, arrive in a usable condition and meet the needs of the equipment burning it.

BMW’s historical project at its South Carolina assembly plant shows that journey at industrial scale. EPA’s project record connects Palmetto Landfill to gas treatment, a pipeline and changing uses inside the factory. The opportunity was a relationship between a waste site and a fuel customer.

The useful question is how the whole route works. More gas volume at one point does not necessarily mean more usable fuel at the destination.

A landfill supplied an industrial neighbor

EPA’s archived BMW project profile, in a collection reviewed in March 2020, describes landfill gas reaching the assembly plant through a 9.5-mile pipeline after filtration and dehydration.

The profile dates the original cogeneration use to 2003. It also records changes: four turbines were replaced by two in 2009, and landfill-gas use in paint-shop burners and a boiler ended in 2012. In the profile’s later historical configuration, incoming landfill gas went to the turbines.

Those dates matter. The case was not one unchanging arrangement in which every past end use operated simultaneously. The customer’s equipment and its use of the gas evolved.

The waste mass is not a metered feed hopper

Landfill gas forms as organic material decomposes under conditions within the waste. The supply is distributed through a heterogeneous mass rather than produced from a freshly prepared, uniform feed delivered to one controlled vessel.

That makes collection a separate engineering job. Gas has to find a path to wells or other collectors and then into a network. The arrangement must work around the landfill’s changing physical conditions.

EPA’s July 2021 handbook chapter on collection-system operation describes the interaction among vacuum, gas movement, cover, liquids and the intended end use. It presents general, site-specific considerations rather than a single operating rule suitable for every landfill.

The distinction from controlled food-waste digestion is useful. A digester can receive a prepared feed on a chosen schedule. A landfill contains material deposited at different times and places, with gas production and collection affected by the conditions around it.

A past waste-delivery total therefore does not, by itself, provide today’s gas flow. Nor does a nominal generating capacity establish the fuel that the wellfield can deliver over a future period.

Cover and collection influence one another

The cover is part of the gas system because it affects the pathways between the waste and the atmosphere. Collection equipment applies vacuum to help move gas into the network.

The connected system has competing concerns. It aims to collect gas while limiting unwanted air entry. Greater extraction effort does not automatically mean that every additional unit of collected volume is newly captured landfill gas.

Air can enter through openings or through the waste and cover. That changes gas composition and can affect conditions in the waste mass. The handbook explains why gas quantity, composition and physical condition have to be understood together.

The appropriate collection balance depends on the actual landfill, its network and its objectives. Cover conditions and the intended fuel use belong in that same physical account.

It does explain why the cover and wellfield are not independent purchases. A change in one can affect the other’s behavior. A collection project has to sustain the physical route that lets useful gas reach the network while meeting the site’s other needs.

A larger volume can contain less methane

Suppose one fictional stream delivers 100 standard-volume units of gas over one hour at 50% methane. It carries 50 standard-volume units of methane. A second delivers 120 units over the same hour at 40% methane, or 48 methane units.

The standard temperature and pressure basis is stipulated to be identical. The second stream has 20% more bulk gas volume and 4% less methane quantity. These are composition assumptions for an illustration, not wellfield targets or measurements from the BMW project.

The point is that a flow reading and a fuel reading describe different aspects of the stream. More volume can include more of something other than methane.

The calculation does not establish heating value, conversion efficiency or capture efficiency. Those require additional evidence and their own defined boundaries. It simply keeps the useful fuel constituent visible within the larger mixture.

For a customer expecting fuel, that distinction has practical consequences. Equipment must handle the delivered volume, while the useful energy depends on composition and the way the equipment converts it. A change can burden the delivery system without providing a proportional increase in useful fuel.

Liquids can interrupt a gas route

Gas collection equipment sits in a landscape that also contains water. Liquids can accumulate in wells or piping, restricting the path available for gas.

The handbook describes the resulting possibility of vacuum being present while little gas is collected. A pressure condition alone does not prove an open, productive flow path.

Settlement creates another connection. As the waste mass changes shape, collection components can move or develop low points. A network that once provided a useful route can acquire a liquid restriction or a damaged section.

This makes maintenance part of fuel supply. The material may still be generating gas while a particular path fails to deliver it. Diagnosing the route is different from assuming that the biological supply has disappeared.

The same reasoning applies farther along the network. Gas that contains moisture must reach the end user in an appropriate condition. Filtration and dehydration in the historical BMW project were therefore part of delivering a usable product, not merely tidying up a stream already ready to burn.

These dependencies help explain why gas collection, liquid management and fuel conditioning need a shared boundary. A problem in one can appear as poor fuel delivery somewhere else.

The customer helps define the product

The BMW profile’s changing end uses make an important business point. “Energy use” is not one uniform destination. A turbine, a boiler and a process burner represent different equipment and service relationships.

The historical project first connected landfill gas to cogeneration and later also to process uses before consolidating its described use back in turbines.

The historical BMW profile makes that route tangible: the pipeline crossed watercourses, an interstate and the company’s test track. A short description such as “use nearby landfill gas” conceals an actual corridor between the two operations.

Collection and energy use have distinct objectives

A collection system can serve environmental-control purposes as well as fuel production. The handbook explicitly distinguishes system objectives and notes that they can be difficult to optimize simultaneously.

A site may need to collect gas from a difficult area even when that stream is less attractive to an energy customer. Conversely, a customer may prefer a stable fuel stream whose composition is easier for its equipment to handle.

Those objectives can overlap without being identical. Treating only the fuel customer’s preferred gas as the project’s entire task would overlook the rest of the landfill. Treating total collection volume as the only objective would overlook the quality needed for energy use.

This is a genuine project tradeoff rather than a reason to abandon recovery. It identifies why the collection system and the energy facility need to be assessed as a connected arrangement with several responsibilities.

It also limits what a generation figure can prove. Electricity produced at a facility does not, by itself, measure all methane generated in the waste or all gas escaping collection. Those require separate observations.

Explore Infinite Upside

For Vijay Sheth’s personal accounts, read Infinite Upside: Building Wealth With Room to Live, published by Sheth Capital, Inc.

Find your edition · Chapter companion

Landfill Airspace and the Years It May Last

Landfill Airspace and the Years It May Last

ABOUT THE CONTRIBUTOR

Luna Lim

DIRECTOR OF FINANCIAL RESEARCH & EDITORIAL STRATEGY

SHETH CAPITAL, INC.

Luna Lim writes about business, investing, and the judgment behind financial decisions. She joined PCH Exotics Inc. as Director of Operations in 2022, working across La Jolla and Miami. Today, she reports directly to Vijay Sheth at Sheth Capital, Inc., bringing an operator’s perspective to the ideas she covers.

Based in Pacific Beach, California, Luna is curious about the people behind the numbers: what they’re building, how they weigh uncertainty, and what makes a risk worth taking. Her articles for Infinite Upside follow those questions through the details, with clear explanations and a feel for how decisions play out in everyday business.

More from Luna Lim

The Infinite Upside store